PRODUCT DETAILS
ZN63-24 Vacuum Circuit Breaker(VS1) is mainly made of solid-sealed poles, and the operating mechanism is optimized to greatly improve the insulation reliability, mechanical reliability and breaking performance of the circuit breaker, and truly achieve the main circuit maintenance-free and Longer mechanical and electrical life; forming system
Listed products to meet different usage requirements.
The installation form of ZN63-24(VS1) Vacuum Circuit Breaker in the switch cabinet can be either fixed type or handcart type.
Z:Vacuum circuit breaker
N:Indoor
63:Design Number
24:Rated voltage:24kV
▢: Rated current:630A、1250A、1600A、2000A、2500A、3150A
▢: Rated short-circuit breaking current:20kA、25kA、31.5kA
1. Ambient air temperature: upper limit +40 degrees, lower limit -40 degrees;
2. Altitude: ≤2000m (if the altitude increases, the rated insulation level will be increased accordingly);
3. Wind pressure: no more than 700Pa (equivalent to wind speed of 34m/s);
4. Earthquake intensity: no more than 8 degrees;
5. Contamination level: Ⅳ level;
6. Maximum daily temperature difference: no more than 25 degrees;
7. Relative humidity: the daily average is not more than 95%, and the monthly average is not more than 90%;
8. Places without inflammability, explosion hazard, chemical corrosion and severe vibration.
Number | Parameter | Unit | Value | |
1 | Rated voltage | kV | 24 | |
2 | Rated insulation level | Rated short-time power frequency withstand voltage (1min) | kV | 65、79 |
(interphase, relative ground, fracture) | ||||
Rated lightning impulse withstand voltage | kV | 125、145 | ||
(phase, phase, port) | ||||
3 | Rated frequency | Hz | 50 | |
4 | Rated current | A | 630、1250、1600、 | |
2000、2500、3150 | ||||
5 | Rated short-circuit breaking current | kA | 20 、25 、31.5 | |
6 | Rated short-time 4s withstand current | 20、 25、 31.5 | ||
7 | Rated short-circuit making current | 50、 63、 80 | ||
8 | Rated peak withstand current | 50 、63、 80 | ||
9 | Nominal Operation Sequence | O-0.3s-CO--180s-CO | ||
10 | Rated short-circuit breaking current breaking times | time | 20 | |
11 | Rated cable charging breaking current | A | 31.5 | |
12 | Rated single capacitor bank breaking current | A | 630 | |
13 | Rated back-to-back capacitor bank breaking current | A | 400 | |
14 | Mechanical life | time | 10000 | |
15 | The moving and static contacts allow the accumulated thickness of wear | mm | 3 | |