¡Bienvenidos amigos extranjeros para visitar nuestra fábrica en China!
Aierway

Aierway ZW32-40.5 Outdoor Vacuum Circuit Breaker

ZW32-40.5kV、35kV、33kV Outdoor Vacuum Circuit Breaker (ZW32-40.5F、ZW32-40.5、ZW32-40.5G) adopts a uniquely designed one-piece solid-sealed pole and a highly reliable operating machine structure. The device is mainly used in medium-voltage overhead line power grids for dividing and combining load current, overload current and...

Tags: zw32

DETALLES DE PRODUCTO

ZW32-40.5kV、35kV、33kV Outdoor Vacuum Circuit Breaker (ZW32-40.5F、ZW32-40.5、ZW32-40.5G) adopts a uniquely designed one-piece solid-sealed pole and a highly reliable operating machine structure. The device is mainly used in medium-voltage overhead line power grids for dividing and combining load current, overload current and short-circuit current.


The upper vacuum circuit breaker is a new 35KV outdoor high-voltage vacuum circuit breaker that replaces the ZW7 vacuum circuit breaker. ZW32 is the miniaturization of ZW7, which is safer and more stable. ZW32-40.5 can also use permanent magnet operating mechanism, cooperate with automation equipment, GPRS, GSM and other remote communication functions to achieve four remote functions such as remote signaling, remote measurement, remote adjustment, and remote control.

Z:Vacuum circuit breaker

W:Outdoor

32:Design Number

40.5:Rated voltage:40.5kV、35kV、33kV

:F:intelligeht type/blank(mannual type)/G:disconnector type

: Rated current:1250A、1600A

: Rated short-circuit breaking current:20kA、31.5kA

1. Ambient air temperature: -30°C~+60°C;

2. Altitude: no more than 3000 meters;

3. The wind speed does not exceed 34m/s;

4. Contamination level: IV;

5. Storage temperature -40°C~+85°C;

Vibration or ground movement from outside the switchgear and control equipment is negligible.

Parameter

unit

value

Rated voltage

kV

40.5、35、33

Rated current

A

1250、1600

Rated frequency

Hz

50/60

Power frequency withstand voltage 1min (wet) (dry) interphase, ground/to fracture

kV

80、95/95

Lightning impulse withstand current (peak value) phase-to-phase, to ground/to fracture

kV

185

Rated short-circuit breaking current

kA

25、31.5

Rated peak withstand current

kA

63、80

Rated short-circuit making current (peak value)

kA

63、80

4s short-time withstand current

kA

25、31.5

Rated operating cycle

O-0.1s-CO-3s-CO-6sCO-60s recover

Rated short-circuit current breaking times

30

Mechanical life

10000

Mechanism Control Voltage

V

AC/DC220

Secondary circuit 1min power frequency withstand voltage

kV

2

0

Aierway ZW32-40.5 Outdoor Vacuum Circuit Breaker