Description
Product introduction
YFV-24KV-800A circui tbreaker has the advantages of easy installation,litle maintenance,long life,small size,low price,safety and reliability.
This product meets technical requirements of GB1984-89,GB/T1984-2003″AC high voltage circuit breaker”.
Major loop:800A-20KA(4s)、25KA(3s),Mechanical life:10000 times.
Ground loop:20KA(2s),Mechanical life:20000 times.
Applying ambient Conditions
Altitude is not more than 1000m,earthquake intensity is not more than 8 degrees.
Pollution resistance level: .
Ambient temperature:-40℃~+140℃,relative humidity daily average≤90%,monthly average≤90%.
Frequentl vibrating installtion sites,places with water vapor,gas,chemical corrosive deposits,salt spray,dust and dit,andfires,that significantly affect the performance of the mechanism and places with fire or explosion hazards are not suitable.
Technical data table 1
No. |
Item |
Unit |
Data |
1 |
Rated frequency |
Hz |
50 |
2 |
Rated current |
A |
630 |
3 |
Rated short time withstand current |
kA |
20/25 |
4 |
Rated peak withstand current |
kA |
50 |
5 |
Rated short circuit duration |
s |
4 |
6 |
Rated short circuit closing current |
kA |
50 |
7 |
Rated operation sequence |
|
O-0.3s-180s-CO |
Technical data table 2
No. |
Item |
Unit |
Data |
1 |
Circuit breaker main loop resistance |
μΩ |
≤30 |
2 |
Overtravel |
mm |
2-3 |
3 |
Spacing |
mm |
8-10 |
4 |
Bounce |
ms |
≤2 |
5 |
Opening average speed |
m/s |
0.6-1.4 |
6 |
Closing average speed |
m/s |
0.4-1.1 |
7 |
Opening three phase asynchronous |
ms |
≤2 |
8 |
Closing three phase asynchronous |
ms |
≤2 |
Outline and dimensions of installation