PRODUCT DETAILS
XGN15 series box-type fixed AC metal-enclosed switchgear is a compact and expandable metal-enclosed ring that uses FLN-12 SF6 load switch as the main switch and the whole cabinet adopts air-insulated, suitable for distribution automation. network switchgear it has the characteristics of simple structure, flexible operation, reliable interlocking and convenient installation. lt can provide satisfactory technical solutions for various applications and different user requirements.
The main switch of XGN15 series box-type fixed AC metal-enclosed switchgear adopts the FLN36-12 type, FLN48-12 type SF6 load switch produced by our company, or the SFG type SF6 load switch produced by ABB company. lt needs to be equipped with VS1 type.VD4/S type, ISM type vacuum circuit breaker or HD4/55 type SF6 circuit breaker. The loads witch and circuit breaker can be operated manually or electrically, and the power distribution automation function can be realized after selecting the electric operating mechanism, PT,CT,FTU and communication device.
Conditions of Use
>Ambient temperature: upper limit +40 Clower limit -15C
>The maximum altitude of the equipment installation site: 1000m;
>Environmental humidity: daily average relative humidity <95%, monthly average relative humidity <90%
>Earthquake heat does not exceed 8 degrees;>The surrounding air should not be significantly polluted by corrosive or combustible gas,water vapor,etc.
>No serious contamination and frequent violent vibration
serial number | project | unit | parameter |
---|---|---|---|
1 | rated voltage | kv | 12 |
2 | rated frequency | hz | 50 |
3 | main busbar rated current | a | 630 |
4 | rated short-time withstand current/duration of main loop and ground loop | ka/s | 20/3,20/20 |
5 | rated peak withstand current of main loop and ground loop | ka | 50 |
6 | rated short-circuit making current of main loop and ground loop | ka | 50 |
7 | load switch full capacity breaking times | number | 100 |
8 | fuse breaking current | ka | 31.5,40,50 |
9 | mechanical life | number | 2000 |
10 | 1min working withstand voltage (rms)time,ground/isolation break | kv | 42/48 |
11 | lightning impulse withstand voltage (peak) phase-to-phase, to ground/isolation fracture | kv | 75/85 |
12 | secondary circuit 1min working frequency withstand voltage | kv | 2 |