AEW-ZN85-40.5ZN85-40.5/T(3AV3)indoor handcar vacuum circuit breaker is suitable for three-phase,Ac50Hzwith 40.5KV rated voltage. It can be used for industrial and mining enterprises, power plants and substations as load current and overload current fault current, and is suitable for the occasion with frequent operation. The circuit breaker adopts an upper and lower arrangement structure to effectively reduce the depth of the circuit breaker. It adopts the composite insulation structure, the three-phase arc extinguishing chamber and the associated electrified body. Separated by three independent epoxy insulation cases, the circuit breaker meets the air distance and creepage requirements under normal operating conditions after the composite insulation structure and it effectively reduces the size of the circuit breaker. The main conductive circuit vacuum interrupter and the dynamic and static conduclive conneclion are installed in the insulation tube, so that the phase to phase distance is only 300mm.The main circuit electrical connections are all fixed connections with high reliability.
Aierway AEW-ZN85-40.5 Indoor Handcart Vacuum Circuit Breaker
Description
Product introduction
AEW-ZN85-40.5ZN85-40.5/T(3AV3)indoor handcar vacuum circuit breaker is suitable for three-phase,Ac50Hzwith 40.5KV rated voltage. It can be used for industrial and mining enterprises, power plants and substations as load current and overload current fault current, and is suitable for the occasion with frequent operation. The circuit breaker adopts an upper and lower arrangement structure to effectively reduce the depth of the circuit breaker. It adopts the composite insulation structure, the three-phase arc extinguishing chamber and the associated electrified body. Separated by three independent epoxy insulation cases, the circuit breaker meets the air distance and creepage requirements under normal operating conditions after the composite insulation structure and it effectively reduces the size of the circuit breaker. The main conductive circuit vacuum interrupter and the dynamic and static conduclive conneclion are installed in the insulation tube, so that the phase to phase distance is only 300mm.The main circuit electrical connections are all fixed connections with high reliability.
Applying ambient Conditions
1.Ambient temperature:-30℃~+40℃.
2.Relative humidity :the average humidity of a day should be no more than95%.The average humidity of a month should be no more than90%.
3.Earthquake intensity : not exceed8 degrees.
4.Saturated vapor pressure :the average pressure of a day should be no more than 2.2kPa;the average pressure o fa month should beno more than1.8Kpa.
5.The height above sea level:≤1000 m(Except special requirements).
6.It should be installed in the places without fire, explosion ,serious filth, and chemical erosion and violent vibration.
Technical data table
No. | Item | Unit | Date |
---|---|---|---|
1 | Rated voltage | KV | 40.5 |
2 | Rated current | A | 1250 | 1600 | 2000 |
3 | Rated short circuit breaking current | KA | 25 | 31.5 | 25 | 31.5 |
4 | Rated dynamic stability current (peak) | KA | 63 | 80 | 63 | 80 |
5 | 4S thermal stability current | KA | 25 | 31.5 | 25 | 31.5 |
6 | Rated short circuit closing current (peak) | KA | 63 | 80 | 63 | 80 |
7 | Rated short circuit current breaking time | Times | 20 |
8 | Rated operating sequence | O-0.3s-CO-180s-CO | |
9 | Rated insulation level
1 min power frequency withstand |
KV | 95
185 |
10 | Mechanical life | Times | 10000 |
11 | Rated single capacitor bank opening and closing current | A | 630 |
12 | Rated back-to-back capacitor bank current | A | 400 |
13 | Rated voltage of energy storage motor | V | AC, DC:110; 220 |
14 | Rated power of energy storage motor | W | ≤230 |
15 | Energy storage time of energy storage motor | S | ≤15 |
16 | Rated voltage of opening and closing coil | V | DC:110; 220 |
17 | Rated current of opening and closing coil | A | 1.05(110V) 0.96(220V) |
18 | Contact stroke | mm | 20±2 |
19 | Contact contact stroke | mm | 7.5±1.5 |
20 | Three-phase opening, closing phase asynchronous | ms | ≤2 |
21 | Contact closing bounce time | ms | ≤3 |
22 | The main circuit resistance (not include the contact arm) | μΩ | ≤40 |
Outline and dimensions of installation