Aierway HXGN17-12 Box type fixed ac metal closed ring network switching equipment

The Aierway HXGN17-12 is an advanced, compact, and fixed-type AC metal-enclosed ring main unit (RMU) designed for indoor three-phase power distribution systems. Engineered for reliable performance in modern medium-voltage networks, it provides safe switching, protection, and control functions in 12kV ring main or radial distribution applications.

描述

Product introduction

The Aierway HXGN17-12 is an advanced, compact, and fixed-type AC metal-enclosed ring main unit (RMU) designed for indoor three-phase power distribution systems. Engineered for reliable performance in modern medium-voltage networks, it provides safe switching, protection, and control functions in 12kV ring main or radial distribution applications.

Key Features

1. Robust & Compact Design
– Fixed Assembly Construction:All primary components are fixed-mounted, ensuring high mechanical stability and reduced maintenance.
– Compact Box-Type Enclosure: Space-saving footprint ideal for substations, industrial plants, and urban network installations with limited space.
– Full Metal Enclosure: Provides IP3X or higher protection against dust, moisture, and accidental contact with live parts.

2. Superior Electrical Performance
– Rated Voltage:** 12kV AC, suitable for standard medium-voltage networks.
– Flexible Current Ratings: Typically available in 630A or 1250A configurations to match various load requirements.
– High Breaking Capacity: Capable of interrupting fault currents up to 25kA or 31.5kA, ensuring network protection under fault conditions.

3. Advanced Switching & Protection
– Load Break Switches: Provide reliable load switching with visible isolation points.
– Fuse Protection:Integrated HV fuses offer cost-effective transformer and feeder protection.

Technical data table 

No. Item Unit FN12-12 FZN25-12
1 Rated Voltage kV 12 12
2 1min Power Frequency Withstand Voltage kV Phase-to-Earth & Phase-to-Phase: 42
Isolation Gap: 48
 Phase-to-Earth & Phase-to-Phase: 42
Isolation Gap: 48
3 Lightning Impulse Withstand Voltage (Peak) kV Phase-to-Earth & Phase-to-Phase: 75
Isolation Gap: 85
Phase-to-Earth & Phase-to-Phase: 75
Isolation Gap: 85
4 Rated Frequency Hz 50 50
5 Rated Current A 630 630
6 Electrical Life at Rated Current Times ≥ 100 ≥ 100
7 No-Load Transformer Breaking Capacity kVA 1250 1250
8 Rated Thermal Withstand Current kA/S 20/4
Earthing Switch: 20/2
20/4
Earthing Switch: 20/2
9 Rated Dynamic Withstand Current (Peak) kA 50 50
10 Rated Short-Circuit Making Current (Peak) kA 50 50
11 Fuse Rated Current A 125 125
12 Rated Transfer Current A 870  870
13 Rated Short-Circuit Breaking Current kA 20 20
14 Matching Fuse Model S□LAJ-12 S□LAJ-12
15 Mechanical Life Times 2000 10000
16 Auxiliary Circuit 1min Power Frequency Withstand Voltage kV 2  2
17 Motor Operating Mechanism Working Voltage V AC/DC 220; 110  AC/DC 220; 110
18 Protection Degree IP2X  IP2X

Outline and dimensions of installation