Aierway 24KV Center Distance 310mm(Fixed type solid sealed pole Terminal)

The Aierway 24kV Center Distance 310mm is an advanced fixed-assembly, solid-insulated switchgear specifically engineered for high-reliability 24kV applications. Its defining feature is the solid-sealed pole terminal design—where vacuum interrupters and main connections are permanently cast in epoxy resin—combined with a generous 310mm phase-to-phase center distance for superior dielectric performance and thermal management. This product is designed for mission-critical installations where maintenance-free operation, maximum safety, and long-term reliability are paramount.

描述

Product introduction

The Aierway 24kV Center Distance 310mm is an advanced fixed-assembly, solid-insulated switchgear specifically engineered for high-reliability 24kV applications. Its defining feature is the solid-sealed pole terminal design—where vacuum interrupters and main connections are permanently cast in epoxy resin—combined with a generous 310mm phase-to-phase center distance for superior dielectric performance and thermal management. This product is designed for mission-critical installations where maintenance-free operation, maximum safety, and long-term reliability are paramount.

Key Advantages of this Design

1. Zero Maintenance: No gas to monitor, no contacts to adjust, no insulation to clean.
2. Absolute Safety: Live parts are completely inaccessible during operation or maintenance.
3. Environmental Immunity: Unaffected by humidity, pollution, altitude, or temperature variations.
4. Exceptional Durability: Solid construction resists vibration, mechanical shock, and thermal stress.

Technical data table 1

Specification Value
Rated voltage 24kV
Rated current 630A, 1250A
Power Frequency Withstand 65kV/79kV
Lightning Impulse Withstand 125 kV
Rated Frequency 50 Hz
Rated short-Circuit Breaking Current 25kA
Rated short-Circuit Breaking Times 30 Times
Rated Peak Withstand Current 63kA
Rated Single Capacitor Bank Breaking Current 630A
Rated Back-to-Back Capacitor Bank Breaking Current 400A
Loop Resistance under Rated Contact Force ≤30Ω
Contact Self-Closing Force 180±50N
Specification Value
Contact opening Distance 12±1mm
Rated Over-Travel 3.5±0.5mm
Average opening speed 1.1±1.7m/s
Average closing speed 0.8±1.2m/s
Rated contact Force 2500±200N
Contact closing Bounce Time ≤2ms
Opening contact Rebound Amplitude ≤2mm

Outline and dimensions of installation