Aierway 40.5KV Ejection

The Aierway 40.5KV Ejection Type Vacuum Circuit Breaker is a state-of-the-art, medium-voltage protection device engineered for high reliability, safety, and ease of maintenance in demanding electrical distribution systems. Featuring a unique ejection mechanism, this breaker combines advanced vacuum interruption technology with robust mechanical design to deliver superior performance in industrial, utility, and infrastructure applications.

描述

Product introduction

The Aierway 40.5KV Ejection Type Vacuum Circuit Breaker is a state-of-the-art, medium-voltage protection device engineered for high reliability, safety, and ease of maintenance in demanding electrical distribution systems. Featuring a unique ejection mechanism, this breaker combines advanced vacuum interruption technology with robust mechanical design to deliver superior performance in industrial, utility, and infrastructure applications.

Key Features & Advantages

1. Ejection Mechanism Design
-Safe & Effortless Operation:** The ejection system allows for smooth, controlled insertion and withdrawal of the breaker from the switchgear compartment with minimal physical effort.
-Clear Position Indication:** Features distinct, mechanically interlocked positions: **CONNECTED, TEST, DISCONNECTED, and EJECTED.** This ensures visual confirmation of the breaker’s status, preventing operational errors.

2. 40.5KV Rated Voltage Class
-Designed for robust performance in standard 35kV/40.5kV distribution networks, meeting the requirements of both IEC (e.g., IEC 62271-100) and relevant ANSI/GB standards.
-Suitable for primary substations, large industrial plants, mining operations, and renewable energy integration points.

Main Technical Parameters

Specification Value
Rated Voltage 40.5kV
Rated Current 2000A, 2500A
Power Frequency Withstand 95kV
Lightning Impulse Withstand 185kV
Rated Frequency 50Hz
Rated Short-Circuit Breaking Current 31.5kA
Rated Short-Circuit Breaking Times 30 Times
Rated Peak Withstand Current 80kA
Rated Single Capacitor Bank Breaking Current 630A
Rated Back-to-Back Capacitor Bank Breaking Current 400A
Loop Resistance under Rated Contact Force ≤25 ~ 30Ω
Contact Self-Closing Force 200±60N
Parameters of Matching Vacuum Switch
Specification Value
Contact opening Distance 20±1mm
Rated Over-Travel 5±1mm
Average Opening Speed 1.7±0.2m/s
Average Closing Speed 0.75±0.2m/s
Rated Contact Force 3600±200N
Contact Closing Bounce Time ≤3ms
Opening Contact Rebound Amplitude ≤2mm

Outline and dimensions of installation