Aierway AEW-ZN85-40.5 Indoor Handcart Vacuum Circuit Breaker

AEW-ZN85-40.5ZN85-40.5/T(3AV3)indoor handcar vacuum circuit breaker is suitable for three-phase,Ac50Hzwith 40.5KV rated voltage. It can be used for industrial and mining enterprises, power plants and substations as load current and overload current fault current, and is suitable for the occasion with frequent operation. The circuit breaker adopts an upper and lower arrangement structure to effectively reduce the depth of the circuit breaker. It adopts the composite insulation structure, the three-phase arc extinguishing chamber and the associated electrified body. Separated by three independent epoxy insulation cases, the circuit breaker meets the air distance and creepage requirements under normal operating conditions after the composite insulation structure and it effectively reduces the size of the circuit breaker. The main conductive circuit vacuum interrupter and the dynamic and static conduclive  conneclion are installed in the insulation tube, so that the phase to phase distance is only 300mm.The main circuit electrical connections are all fixed connections with high reliability.

Description

Product introduction

AEW-ZN85-40.5ZN85-40.5/T(3AV3)indoor handcar vacuum circuit breaker is suitable for three-phase,Ac50Hzwith 40.5KV rated voltage. It can be used for industrial and mining enterprises, power plants and substations as load current and overload current fault current, and is suitable for the occasion with frequent operation. The circuit breaker adopts an upper and lower arrangement structure to effectively reduce the depth of the circuit breaker. It adopts the composite insulation structure, the three-phase arc extinguishing chamber and the associated electrified body. Separated by three independent epoxy insulation cases, the circuit breaker meets the air distance and creepage requirements under normal operating conditions after the composite insulation structure and it effectively reduces the size of the circuit breaker. The main conductive circuit vacuum interrupter and the dynamic and static conduclive  conneclion are installed in the insulation tube, so that the phase to phase distance is only 300mm.The main circuit electrical connections are all fixed connections with high reliability.

Applying ambient Conditions

1.Ambient temperature:-30℃~+40℃.

2.Relative humidity :the average humidity of a day should be no more than95%.The average humidity of a month should be no more than90%.

3.Earthquake intensity : not exceed8 degrees.

4.Saturated vapor pressure :the average pressure of a day should be no more than 2.2kPa;the average pressure o fa month should beno more than1.8Kpa.

5.The height above sea level:≤1000 m(Except special requirements).

6.It should be installed in the places without fire, explosion ,serious filth, and chemical erosion and violent vibration.

Technical data table 

No. Item Unit Date
1 Rated voltage KV 40.5
2 Rated current A 1250 | 1600 | 2000
3 Rated short circuit breaking current KA 25 | 31.5 | 25 | 31.5
4 Rated dynamic stability current (peak) KA 63 | 80 | 63 | 80
5 4S thermal stability current KA 25 | 31.5 | 25 | 31.5
6 Rated short circuit closing current (peak) KA 63 | 80 | 63 | 80
7 Rated short circuit current breaking time Times 20
8 Rated operating sequence O-0.3s-CO-180s-CO
9 Rated insulation level

1 min power frequency withstand
Lightning impulse withstand voltage

KV 95

185

10 Mechanical life Times 10000
11 Rated single capacitor bank opening and closing current A 630
12 Rated back-to-back capacitor bank current A 400
13 Rated voltage of energy storage motor V AC, DC:110; 220
14 Rated power of energy storage motor W ≤230
15 Energy storage time of energy storage motor S ≤15
16 Rated voltage of opening and closing coil V DC:110; 220
17 Rated current of opening and closing coil A 1.05(110V) 0.96(220V)
18 Contact stroke mm 20±2
19 Contact contact stroke mm 7.5±1.5
20 Three-phase opening, closing phase asynchronous ms ≤2
21 Contact closing bounce time ms ≤3
22 The main circuit resistance (not include the contact arm) μΩ ≤40

Outline and dimensions of installation

AEW-ZN85-40.5