Product introduction
XGN66-12 box type fixed metal enclosed switchgear (hereinafter referred to as switchgear) is suitable for use as a device for receiving and distributing electrical energy in 3.6-12kV three-phase AC 50Hz systems, and is suitable for frequent operation places and switchgear retrofit with oil switches. The busbar system consists of a single busbar system and a single busbar segmented system.
The switchgear meets the requirements of GB3906 “3.6~40.5kV AC Metal Enclosed Switchgear and Control Equipment” and DL404 “Technical Conditions for Ordering Indoor AC High Voltage Switchgear”. The switchgear has a beautiful appearance, small size, and complete and reliable anti misoperation function. The main switch VS1-12 or ZN28-12 vacuum circuit breaker installed in the switchgear adopts GN30-12 and GN19-10 isolating switches, and the grounding switch adopts JN15-12 grounding switch.
Key Features
1.Robust Enclosure: Fully metal-enclosed structure ensuring safety and durability.
2.Fixed Installation: Components are fixed-mounted, offering high reliability and simplified maintenance.
3.Compact Design: Space-saving box-type layout suitable for constrained environments.
4.Wide Compatibility: Compatible with various switching and protection devices (e.g., circuit breakers, load break switches).
Technical data table
| No. | Item | Unit | Parameter |
|---|---|---|---|
| 1 | Rated Voltage | kV | 3.6, 7.2, 12 |
| 2 | Rated Current | A | 630, 1250 |
| 3 | Rated Short-Circuit Breaking Current | kA | 20, 25, 31.5 |
| 4 | Rated Short-Circuit Making Current | kA | 50, 63, 80 |
| 5 | Rated Short-Time Withstand Current (4s RMS) | kA | 20, 25, 31.5 |
| 6 | Rated Peak Withstand Current (Peak) | kA | 50, 63, 80 |
| 7 | 1min Power Frequency Withstand Voltage | kV | 42 |
| 8 | Lightning Impulse Withstand Voltage | kV | 75 |
| 9 | Auxiliary Circuit 1min Power Frequency Withstand Voltage | kV | 2 |
| 10 | Protection Class | – | IP3X |
| 11 | Overall Dimensions (Cable Outlet, Width × Depth × Height) | mm | 900 × 1000 × 2300 |
Typical Scheme